APPENDIX A – FAILURE CODES OF THE PSBEN 13,8V POWER SUPPLY
Technical
output
activation
- No AC mains supply
- F
MAIN
fuse failure
- Blown F
AUX
fuse
- AUX output overload
- Blown F
BAT
fuse
- Short circuit in the battery circuit
- Short circuit in the AUX output circuit
- Worn out batteries
- Undercharged batteries
- Battery not connected
- The output voltage of the PSU over 14.7V
Battery charging
circuit failure!
- The output voltage of the PSU set too low , below
13V
- Battery charging circuit failure
- The output voltage below 11.8V (during buffer
operation)
- The battery voltage has dropped below 11.5V
(during battery-assisted operation)
Low battery voltage –
off!
- the battery voltage has dropped below 10V (during
battery-assisted operation)
- Activation of the input of collective failure: EXT IN
Internal damage of the
PSU.
- no communication with LCD panel